1298
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
The input value (E1) is output with a delay by the dead time according to the content of the operation control signal (e1).
SN: Sampling count, ST: Data collection interval, E1: Input value, YS: Initial output value
The S.DED instruction performs the following operations.
*1 Least recent data is an input value (E1) after SN.
• When the dead time table does not have sufficient data, the data sufficiency bit (BB1) is set to 1.
• When the sampling count (SN) is 0, the data sufficiency bit (BB1) is 0 and the output value (BW) equals the input value
(E1).
SN: Dead time table
e1 OCHG Dead time BW
10/1 E1
100 STSN Up to SN E1 when e1 changed from 1 to 0
After SN Least recent data
*1
1 Up to SN YS
After SN Least recent data
*1
000/1 STSN Least recent data
*1
Error code (SD0) Error content
3400H An invalid operation (such as division by zero) is performed.
3402H The value specified by (s1) or (s2) is a subnormal number or NaN (not a number).
3403H An overflow has occurred.
3405H The execution cycle (T) setting is less than 0.
The sampling count (SN) is less than 0 or greater than 48.
The data sampling interval (ST) is less than 0.
(Data sampling interval (ST)execution cycle (T)) is greater than 32767.
e1
BB1
SN
SN
E1, Y1
ST1 ST2 ST3 ST4 ST5 ST6 ST7
Ys
E1
Y1
SN1
SN3
SN2
SN