Technical specifications
A.2 General technical specifications
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1363
Note
The S7
-1200 automation system is intended for use in industrial areas; use in residential
areas can have an impact on radio or TV reception. If you use the S7
-1200 in residential
areas, you must ensure that its radio inte
rference emission complies with the limit value
Class B in accordance with EN 55011.
Examples of suitable measures for achieving RF interference, level Class B include:
-
Installation of the S7-1200 in a grounded control cabinet
-
Use of noise filters in the supply lines
Ensure that the radio interference emission complies with Class B in accordance with EN
55011.
Individual acceptance is required (final installation must meet all safety and EMC
requirements of a residential installation).
Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as
intended in an electromagnetic environment and to operate without emitting levels of
electromagnetic interference (EMI) that may disturb other electrical devices in the vicinity.
Table A- 2 Immunity per EN 61000-6-2
Electromagnetic compatibility - Immunity per EN 61000-6-2
EN 61000-4-2
Electrostatic discharge
8 kV air discharge to all surfaces
6 kV contact discharge to exposed conductive surfaces
EN 61000-4-3
Radiated, radio-frequency, elec-
tromagnetic field immunity test
80 to 1000 MHz, 10 V/m, 80% AM at 1 kHz
1.4 to 2.0 GHz, 3 V/m, 80% AM at 1 kHz
2.0 to 2.7 GHz, 1 V/m, 80% AM at 1 kHz
EN 61000-4-4
Fast transient bursts
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to I/O
EN 6100-4-5
Surge immunity
AC systems - 2 kV common mode, 1 kV differential mode
DC systems - 2 kV common mode, 1 kV differential mode
For DC systems, refer to Surge immunity below
EN 61000-4-6
Conducted disturbances
150 kHz to 80 MHz, 10 V RMS, 80% AM at 1kHz
EN 61000-4-11
Voltage dips
AC systems
0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles at 60
Hz