Table A- 3 Conducted and radiated emissions per EN 61000-6-4
Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4
Conducted Emissions
EN 55016, Class A, Group 1
<79dB (μV) quasi-peak; <66 dB (μV) average
0.5 MHz to 5 MHz <73dB (μV) quasi-peak; <60 dB (μV) average
<73dB (μV) quasi-peak; <60 dB (μV) average
Radiated Emissions
EN 55016, Class A, Group 1
30 MHz to 230 MHz <40dB (μV/m) quasi-peak; measured at 10m
<47dB (μV/m) quasi-peak; measured at 10m
< 76dB (uV/m) quasi peak, measured at 10m
Wiring systems subject to surges from lightning strike coupling must be equipped with
external protection. One specification for evaluation of protection from lightning type surges
is found in EN 61000-4-5, with operational limits established by EN 61000-6-2. S7-1200 DC
CPUs and signal modules require external protection to maintain safe operation when
subject to surge voltages defined by this standard.
Listed below are some devices that support the needed surge immunity protection. These
devices only provide the protection if they are properly installed according to the
manufacturer's recommendations. Devices manufactured by other vendors with the same or
better specifications can also be used:
Table A- 4 Devices that support surge immunity protection
BLITZDUCTOR VT, BVT AVD 24, Part Number 918 422
DEHNpatch DPA M CLE RJ45B 48, Part Number 929 121
RS-485
BLITZDUCTOR XT, Basic Unit BXT BAS, Part Number 920 300
BLITZDUCTOR XT, Module BXT ML2 BD HFS 5, Part Number 920 271
RS-232
BLITZDUCTOR XT, Basic Unit BXT BAS, Part Number 920 300
BLITZDUCTOR XT, Module BXT ML2 BE S 12, Part Number 920 222
DEHN, Inc., Type DCO SD2 E 24, Part Number 917 988
+24 V DC digital outputs
DEHN, Inc., Type DCO SD2 E 24, Part Number 917 988