Technical specifications
A.9 Digital signal modules (SMs)
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1457
SM 1223 DI 8 x 120/230 V AC / DQ 8 x Relay
Connection of 2 wire proximity sensor (Bero)
1 mA
Cable length Unshielded: 300 meters
Shielded: 500 meters
Number of inputs on simultaneously
1
Channels within a group must be of the same phase.
Table A- 134 Digital outputs
SM 1223 DI 8 x 120/230 V AC / DQ 8 x Relay
5 to 30 V DC or 5 to 250 V AC
Logic 1 signal at max. current
Logic 0 signal with 10K Ω load
ON state contact resistance
Leakage current per point
Isolation (field side to logic) 1500 V AC (coil to contact)
Isolation groups 2
Current per common (max.)
Maximum relay switching frequency
Lifetime mechanical (no load)
10,000,000 open/close cycles
Lifetime contacts at rated load
1000,000 open/close cycles
Last value or substitute value (default value 0)
Number of outputs on simultaneously
• 4 (no adjacent points) at 60 °C horizontal or 50 °C vertical
• 8 at 55 °C horizontal or 45 °C vertical
500 m shielded, 150 m unshielded