EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 1467

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.10 Analog signal modules (SMs)
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
1467
Model
SM 1234 AI 4 x 13 bit / AQ 2 x 14 bit
Isolation (field side to logic)
None
Accuracy (25 °C / -20 to 60 °C) ±0.1% / ±0.2% of full scale
Analog to digital conversion time
625 μs (400 Hz rejection)
Common mode rejection 40 dB, DC to 60 Hz
Operational signal range
1
Signal plus common mode voltage must be less than +12 V and greater
than -12 V
Cable length (meters)
100 m, twisted and shielded
1
Voltages outside the operational range applied to one channel may cause interference on other channels.
Table A- 153 Analog outputs
Technical data
SM 1234 AI 4 x 13 bit / AQ 2 x 14 bit
Number of outputs
2
Type
Voltage or current
Range
±10 V or 0 to 20 mA
Resolution
Voltage: 14 bits ; Current: 13 bits
Full scale range (data word) Voltage: -27648 to 27648; Current: 0 to 27648
Refer to the section on output ranges for voltage and current
(Page 1472).
Accuracy (25 °C / -20 to 60 °C)
±0.3% / ±0.6% of full scale
Settling time (95% of new value) Voltage: 300 μs (R), 750 μs (1 uF)
Current: 600 μs (1 mH), 2 ms (10 mH)
Load impedance Voltage: ≥ 1000 Ω
Current: ≤ 600 Ω
Maximum output short circuit current Voltage mode: ≤ 24 mA
Current mode: ≥ 38.5 mA
Behavior on RUN to STOP Last value or substitute value (default value 0)
Isolation (field side to logic)
none
Isolation (24 V to output) none
Cable length (meters)
100 m twisted and shielded
Table A- 154 Diagnostics
Model
SM 1234 AI 4 x 13 bit / AQ 2 x 14 bit
Overflow/underflow
Yes
Short to ground (voltage mode only)
Yes on outputs
Wire break (current mode only)
Yes on outputs
24 V DC low voltage
Yes

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals