Technical specifications
A.11 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
1474 System Manual, V4.2, 09/2016, A5E02486680-AK
Table A- 165 Diagnostics
1
Wire break
2, 3
Yes
1
The overflow, underflow and low voltage diagnostic alarm information will be reported in the analog data values even if
the alarms are disabled in the module configuration.
When wire break alarm is disabled and an open wire condition exists in the sensor wiring, the module may report ran-
dom values.
The module performs wire break testing every 6 seconds, which extends the update time by 9 ms for each enable
channel once every 6 seconds.
The SM 1231 Thermocouple (TC) analog signal module measures the value of voltage
connected to the module inputs. The temperature measurement type can be either
"Thermocouple" or "Voltage".
● "Thermocouple": The value will be reported in degrees multiplied by ten (for example, 25.3
degrees will be reported as decimal 253).
● "Voltage": The nominal range full scale value will be decimal 27648.
Table A- 166 Wiring diagrams for the thermocouple SMs
SM 1231 AI 4 x TC 16 bit (6ES7231-5QD32-0XB0)
SM 1231 AI 8 x TC bit (6ES7231-5QF32-0XB0)
Note: Connectors must be gold. See Appendix C, Spare Parts for article number.
① TC 2, 3, 4, and 5 not shown connected for clarity.