EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 601

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
601
Table 10- 23 Data types for the parameters
Parameter and type
Data type
Description
Setpoint
IN
Real
Setpoint of the PID controller in automatic mode. (Default value: 0.0)
Input IN Real A tag of the user program is used as the source of the process value.
(Default value: 0.0)
If you are using the Input parameter, you must set Con-
fig.InputPerOn = FALSE.
Input_PER IN Word An Analog input is used as the source of the process value. (Default
value: W#16#0)
If you are using the Input_PER parameter, you must set Con-
fig.InputPerOn = TRUE.
Actuator_H IN Bool Digital position feedback of the valve for the high end stop
If Actuator_H =
TRUE, the valve is at the high end stop and is no longer
moved in this direction. (Default value: FALSE)
Actuator_L IN Bool Digital position feedback of the valve for the low end stop
If Actuator_L = TRUE, the valve is at the low end stop and is no longer
moved in this direction. (Default value: FALSE)
Feedback IN Real Position feedback of the valve. (Default value: 0.0)
If you are using the Feedback parameter, you must set Con-
fig.FeedbackPerOn = FALSE.
Feedback_PER IN Int Analog feedback of the valve position. (Default value: W#16#0)
If you are using the Feedback_PER parameter, you must set Con-
fig.FeedbackPerOn = TRUE. Feedback_PER is scaled, based upon the
following tags:
Config.FeedbackScaling.LowerPointIn
Config.FeedbackScaling.UpperPointIn
Config.FeedbackScaling.LowerPointOut
Config.FeedbackScaling.UpperPointOut
Disturbance
IN
Real
Disturbance variable or pre-control value
ManualEnable IN Bool Enables or disables the manual operation mode. (Default value:
FALSE):
A FALSE to TRUE edge activates "manual mode", while State = 4,
Mode remains unchanged.
As long as ManualEnable = TRUE, you cannot change the operat-
ing mode using a rising edge at ModeActivate or use the commis-
sioning dialog.
A TRUE to FALSE edge activates the operating mode that is as-
signed by Mode.
Note: We recommend that you change the operating mode using
ModeActivate only.
ManualValue IN Real Process value for manual operation. (Default value: 0.0)
In manual mode, you specify the absolute position of the valve. Manu-
alValue is evaluated only if you are using OutputPer,
or
if position feed-
back is available.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals