EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 602

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
602 System Manual, V4.2, 09/2016, A5E02486680-AK
Parameter and type
Data type
Description
ManualUP IN Bool
Manual_UP = TRUE:
The valve is opened even if you use Output_PER or a position
feedback. The valve is no longer moved if the high end stop has
been reached.
See also Config.VirtualActuatorLimit
Manual_UP = FALSE:
If you use Output_PER or a position feedback, the valve is
moved to ManualValue. Otherwise, the valve is no longer
moved.
Note: If Manual_UP and Manual_DN are set to TRUE simultaneously,
the valve is not moved.
ManualDN IN Bool
Manual_DN = TRUE:
The valve is opened even if you use Output_PER or a position
feedback. The valve is no longer moved if the high end stop has
been reached.
See also Config.VirtualActuatorLimit
Manual_DN = FALSE:
If you use Output_PER or a position feedback, the valve is
moved to ManualValue. Otherwise, the valve is no longer
moved.
ErrorAck
IN
Bool
Resets the ErrorBits and warning outputs. FALSE to TRUE edge
Reset IN Bool Restarts the controller. (Default value: FALSE):
FALSE to TRUE edge:
Switches to "inactive" mode
Resets the ErrorBits and warning outputs
Clears Integral action
Maintains PID parameters
As long as Reset = TRUE, PID_3Step remains in "Inactive" mode
(State = 0).
TRUE to FALSE edge:
PID_3Step switches to the operating mode that is saved in the
Mode parameter.
ModeActivate IN Bool The PID_3Step switches to the mode that is saved in the Mode param-
eter. FALSE to TRUE edge:
Mode IN Int The desired PID mode; Activated on the leading edge of the Mode
Activate input.
ScaledInput
OUT
Real
Scaled process value
ScaledFeedback OUT Real Scaled valve position feedback
Note: For an actuator without position feedback, the position of the
actuator indicated by ScaledFeedback is very imprecise. ScaledFeed-
back can only be used for rough estimation of the current position in
this case.
Output_UP OUT Bool Digital output value for opening the valve. (Default value: FALSE)
If Config.OutputPerOn = FALSE, the parameter Output_UP is used.
Output_DN OUT Bool Digital output value for closing the valve. (Default value: FALSE)
If Config.OutputPerOn = FALSE, the parameter Output_DN is used.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals