EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 603

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
603
Parameter and type
Data type
Description
Output_PER OUT Word Analog output value.
If Config.OutputPerOn = TRUE, the parameter Output_PER is used.
SetpointLimitH OUT Bool Setpoint high limit. (Default value: FALSE)
If SetpointLimitH = TRUE, the absolute upper limit of the setpoint is
reached (Setpoint ≥ Config.SetpointUpperLimit).
Note: The setpoint is limited to (Setpoint ≥ Config.SetpointUpperLimit).
SetpointLimitL OUT Bool Setpoint low limit. (Default value: FALSE)
If SetpointLimitL = TRUE, the absolute lower limit of the setpoint is
reached (Setpoint ≥ Config.SetpointLowerLimit).
Note: The setpoint is limited to (Setpoint ≥ Config.SetpointLowerLimit).
InputWarningH OUT Bool If InputWarningH =
TRUE, the input value has reached or exceeded the
warning high limit. (Default value: FALSE)
InputWarningL OUT Bool If InputWarningL = TRUE, the input value has reached or exceeded the
warning low limit. (Default value: FALSE)
State OUT Int Current operating mode of the PID controller. (Default value: 0)
You can change the operating mode using the Mode input parameter
and a rising edge at ModeActivate:
State = 0: Inactive
State = 1: Pre-tuning
State = 2: Manual fine tuning
State = 3: Automatic mode
State = 4: Manual mode
State = 5: Substitute output value approach
State = 6: Transition time measurement
State = 7: Error monitoring
State = 8: Substitute output value approach with error monitoring\
State = 10: Manual mode without end stop signals
Error OUT Bool If Error = TRUE, at least one error message is pending. (Default value:
FALSE)
Note: The Error parameter in V1.x PID was the ErrorBits field that con-
tained the error codes. It is now a Boolean flag indicating that an error
has occurred.
ErrorBits OUT DWord The PID_3Step instruction ErrorBits parameters table (Page 607) de-
fines the error messages that are pending. (Default value:
DW#16#0000 (no error)). ErrorBits is retentive and is reset upon a
rising edge at Reset or ErrorAck.
Note: In V1.x, the ErrorBits parameter was defined as the Error param-
eter and did not exist.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals