EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 611

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
611
Table 10- 27 Data types for the parameters
Parameter and type
Data type
Description
Setpoint
IN
Real
Setpoint of the PID controller in automatic mode. (Default value: 0.0)
Input IN Real A tag of the user program is used as the source of the process value.
(Default value: 0.0)
If you are using the Input parameter, you must set Con-
fig.InputPerOn = FALSE.
Input_PER IN Int An Analog input is used as the source of the process value. (Default
value: 0)
If you are using the Input_PER parameter, you must set Con-
fig.InputPerOn = TRUE.
Disturbance
IN
Real
Disturbance variable or pre-control value
ManualEnable IN Bool Enables or disables the manual operation mode. (Default value:
FALSE):
A FALSE to TRUE edge activates Manual mode, while State = 4,
Mode remains unchanged.
As long as ManualEnable = TRUE, you cannot change the operat-
ing mode using a rising edge at ModeActivate or use the commis-
sioning dialog.
A TRUE to FALSE edge activates the operating mode that is as-
signed by Mode.
Note: We recommend that you change the operating mode using
ModeActivate only.
ManualValue IN Real Output value for manual operation. (Default value: 0.0)
You can use values from Config.OutputLowerLimit to Con-
fig.OutputUpperLimit.
ErrorAck IN Bool Resets the ErrorBits and warning outputs with a FALSE to TRUE edge.
(Default value: FALSE)
Reset IN Bool Restarts the controller. (Default value: FALSE):
FALSE to TRUE edge:
Switches to "inactive" mode
Resets the ErrorBits and warning outputs
Clears Integral action
Maintains PID parameters
As long as Reset = TRUE, PID_Temp remains in Inactive mode
(State = 0).
TRUE to FALSE edge:
PID_Temp switches to the operating mode that is saved in the
Mode parameter.
ModeActivate IN Bool The PID_Temp switches to the operating mode that is saved in the
Mode parameter with a FALSE to TRUE edge. (Default value: FALSE)

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals