EasyManua.ls Logo

Siemens SIMATIC S7-1200 - Page 612

Siemens SIMATIC S7-1200
1614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology instructions
10.2 PID control
S7-1200 Programmable controller
612 System Manual, V4.2, 09/2016, A5E02486680-AK
Parameter and type
Data type
Description
Mode IN/OUT Int Activated on the leading edge of the Mode Activate input.
Operating mode selection (Default value: 0.0):
Mode = 0: Inactive
Mode = 1: Pretuning
Mode = 2: Fine tuning
Mode = 3: Automatic mode
Mode = 4: Manual mode
“Substitute output value with error monitoring” (State = 5). This cannot
be activated by the user; it is only an automatic error reaction.
Master
IN/OUT
DWord
Cascade connection to master (AntiWindUp and tuning conditions).
(Default value: DW#16#0000)
Bits 0 - 15: Not used in PID_Temp instruction
Bits 16 - 23: Limit counter: A slave increments this value if it reach-
es its limitation. The number of slaves in limitation is processed for
Anti-Windup-functionality (Refer to the Con-
fig.Cascade.AntiWindUpMode parameter.
Bit 24: IsAutomatic: This bit is set to "1" if all slaves of this controller
are in Automatic mode and are processed to check conditions for
tuning in a cascade. This bit is identical to the AllSlaveAutomat-
icState parameter.
Bit 25: "IsReplacement-Setpoint": This bit is set to "1" if a slave of
this controller has the "Replacement Setpoint" activated and is pro-
cessed to check conditions for tuning in a cascade. The inverted
value is stored in the NoSlaveReplacementSetpoint parameter.
Slave IN/OUT DWord
ScaledInput
OUT
Real
Scaled process value. (Default value: 0.0)
OutputHeat
1
OUT Real Output value for heating in REAL format. (Default value: 0.0)
This output value is calculated, independent from the output selection,
using the Config.Output.Heat.Select parameter.
OutputCool
1
OUT Real Output value for cooling in REAL format. (Default value: 0.0)
This output value is calculated, independent from the output selection,
using the Config.Output.Cool.Select parameter.
OutputHeat_PER
1
OUT Int Output value for heating in peripheral format (Default value: 0)
This output value is only calculated if selected using the Con-
fig.Output.Heat.Select = 2 parameter. If not selected, this output is
always "0".
OutputCool_PER
1
OUT Int Output value for cooling in peripheral format (Default value: 0)
This output value is only calculated if selected using the Con-
fig.Output.Cool.Select = 2 parameter. If not selected, this output is
always "0".
OutputHeat_PWM
1
OUT Bool Pulse-width-modulated output value for heating. (Default value: FALSE)
This output value is only calculated if selected using the Con-
fig.Output.Heat.Select = 1 (default value) parameter. If not selected,
this output is always FALSE.

Table of Contents

Other manuals for Siemens SIMATIC S7-1200

Related product manuals