Communication
11.2 PROFINET
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
893
Return val-
ue
STATUS*
(W#16#...):
Explanation
Notes
8012 Error receiving the data You will find further information on evaluation
in the SFB_STATUS parameter of the instance
data block. The error code displayed at the
SFB_STATUS parameter is explained in the
STATUS parameter description for the TRCV
(Page 857) instruction.
8013 Error during connection establishment You will find further information on evaluation
in the SFB_STATUS parameter of the instance
data block. The error code displayed at the
SFB_STATUS parameter is explained in the
STATUS parameter description for the TCON
(Page 857) and TDISCON (Page 857) instruc-
tions.
8014 Establishment of a connection is not
possible.
You may have entered an incorrect mail server
IP address (MailServerAddress (Page 890)) or
too short a time span (WatchDogTime
(Page 890)) for connection establishment. It is
also possible that the CPU has no connection
to the network or that the CPU configuration is
incorrect.
8015 Incorrect data type for
MAIL_ADDR_PARAM
The only valid data types are the system data
types (structures) Tmail_v4 and TMail_FQDN.
8016 Incorrect data type for the
ATTACHMENT parameter
The only valid data types are ArrayOfByte,
ArrayOfWord and ArrayOfDWord.
8017 Incorrect data length for the
ATTACHMENT parameter
Data length must be <= 65534 bytes.
82xx, 84xx,
or 85xx
The error message originates from
the mail server and corresponds,
except for the "8", to the error number
of the SMTP protocol.
The following lines list several error
codes that can occur.
You will find more detailed information on the
SMTP error code and other error codes in the
SMTP protocol on the Internet or in the error
documentation of the mail server. You can
also view the most recent error message from
the mail server in your instance DB in the
BUFFER1 parameter. You will find the last
data sent by the TMAIL_C instruction under
DATEN in the instance DB.
8450 Action not executed: Mailbox not
available/cannot be reached
Try again later.
8451
Action aborted: Local processing error
Try again later.
8500 Syntax error: Error not recognized.
This also includes the error when a
command string is too long. This can
also occur when the e-mail server
does not support the LOGIN authenti-
cation procedure.
Check the parameters of TMAIL_C. Try to
send an e-mail without authentication. To do
this, replace the content of the UserName
parameter with an empty string. If no user
name is specified, the LOGIN authentication
procedure is not used.
8501 Syntax error: Incorrect input at a pa-
rameter
Possible cause: Incorrect address at the TO_S
or CC parameter (see also: TO_S and CC
parameters (Page 891)).