Communication
11.2 PROFINET
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
903
The following table shows the possible values for the parameters STATUS and ERR_LOC:
STATUS*
ERR_LOC*
Explanation
0000_0000
0000_0000
Order processing completed without errors.
0070_0000 0000_0000 No job processing active.
0070_0100
0000_0000
Start of the order processing.
0070_0200
0000_0000
Intermediate call (REQ irrelevant).
C08x_yy00
0000_0000
General error information.
C080_8000 0000_0000 Error at call of the instruction:
The hardware ID at the parameter Interface is invalid.
C080_8100 0000_0000 Error at call of the instruction:
The hardware ID at the parameter Interface does not address a PROFINET interface.
C080_8700 0000_0000 Error at call of the instruction:
Incorrect length of the data block at the parameter CONF_DATA.
C080_8800 0001_0000 Error in the system data type IF_CONF_HEADER:
The parameter FieldType has an invalid value. Use the value "0" for FieldType.
C080_8900 0001_0000 Error in the system data type IF_CONF_HEADER:
The parameter FieldId has an invalid value or was used several times. Use the value "0" for
FieldId.
C080_8A00 0001_0000 Error in the system data type IF_CONF_HEADER:
Incorrect number at the parameter SubfieldCount. Enter the correct number of system data
types IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP being used.
C080_8B00 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
The parameter Id has an invalid value. For IF_CONF_V4 use "30", for IF_CONF_NOS "40",
for IF_CONF_NTP "17".
C080_8C00 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
Incorrect data type system used, wrong order or multiple use of a system data type.
C080_8D00 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
The parameter Length has an incorrect or invalid value.
C080_8E00 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
The parameter Mode has an incorrect or invalid value.
With IF_CONF_V4 and IF_CONF_NOS only the values "1" (permanent) or "2" (tempo-
rary) are permitted.
With IF_CONF_NTP only the value "2" (temporary) is permitted.
C080_9000 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
Configuration data cannot be applied. Possible cause:
With IF_CONF_V4: In the hardware configuration, the setting "Set IP address on the
device" was not selected..
With IF_CONF_NOS: In the hardware configuration, the setting "Set PROFINET device
name on the device" was not selected..
With IF_CONF_NTP: In the hardware configuration, the setting "Enable time synchroni-
zation via NTP server " was not selected and no IP address was set for NTP servers..
C080_9400 0001_000x Error in the system data type IF_CONF_V4, IF_CONF_NOS, or IF_CONF_NTP:
A parameter value is undefined or invalid.