n
F6-22: DeviceNet PCA Setting
Parameter Overview
No. Name Description Range Default
F6-22 DeviceNet PCA Setting I/O Polled Consuming Assembly Data Instance 0 to 255 0
n
F6-23: DeviceNet PPA Setting
Parameter Overview
No. Name Description Range Default
F6-23 DeviceNet PPA Setting I/O Polled Producing Assembly Data Instance 0 to 255 0
n
F6-24: DeviceNet Idle Mode Fault Detection
Parameter Overview
No. Name Description Range Default
F6-24 DeviceNet Idle Mode Fault Detection
Selects if a fault is detected during communication idle mode.
0: Disabled
1: Enabled
0 or 1 0
n
F6-30: PROFIBUS Node Address
Parameter Overview
No. Name Description Range Default
F6-30 PROFIBUS Node Address Sets the node address for a PROFIBUS option. 0 to 125 0
n
F6-31: PROFIBUS Clear Mode Selection
Parameter Overview
No. Name Description Range Default
F6-31 PROFIBUS Clear Mode Selection
Selects the operation when a "Clear Mode" command is received.
0: Resets back to zero.
1: Maintains the previous value.
0 or 1 0
n
F6-32: PROFIBUS Map Selection
Parameter Overview
No. Name Description Range Default
F6-32 PROFIBUS Map Selection
0: PPO Type
1: Conventional
0 or 1 0
n
F6-36: CANopen Node ID Selection
Parameter Overview
No. Name Description Range Default
F6-36 CANopen Node ID Selection Sets the Node ID for a CANopen option 0 to 127 99
n
F6-37: CANopen Communication Speed
Parameter Overview
No. Name Description Range Default
F6-37 CANopen Communication Speed
0: Auto-adjust
1: 10kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
0 to 8 6
n
F6-40: CompoNet Node ID
Parameter Overview
No. Name Description Range Default
F6-40 CompoNet Node ID Sets the Node ID for a CompoNet option. 0 to 63 0
n
F6-41: CompoNet Speed
Parameter Overview
5.6 F: Option Settings