No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
PM
b1-03 Stopping Method Selection
Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer
(A new run command is ignored if received before the timer expires)
0 to 3 0 S S S 182 78
DC Injection Braking at Stop cannot be selected when using
Open Loop Vector for PM motors.
b1-04 Reverse Operation Selection
Permits or prohibits reverse operation.
0: Reverse enabled.
1: Reverse disabled.
0, 1 0 A A A 183 —
b1-07 Local/Remote Run Selection
Determines the operation when the Run command source is switched from
LOCAL to REMOTE or between Run source 1 and 2 while an external Run
command is active at the new source.
0: External Run command has to be cycled at the new source to be activated.
1: External Run command at new source is accepted immediately.
0, 1 0 A A A 186 —
b1-08
Run Command Selection while in
Programming Mode
0: Run command accepted only in the operation menu.
1: Run command accepted in all menus.
2: Prohibit entering programming mode during Run
0 to 2 0 A A A 187 —
b1-14 Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2 and W/T3.
0: Standard
1: Switch phase order
0, 1 0 A A A 1C3 —
b1-15 Frequency Reference 2
Selects the frequency reference input source.0: Operator - Digital preset speed
d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
0 to 4 0 A A A 1C4 —
b1-16 Run Command Source 2
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
0 to 3 0 A A A 1C5 —
b1-17 Run Command at Power Up
Determines the operation when a Run command is active at power up of the drive.
0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
0, 1 0 A A A 1C6 —
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-01 DC Injection Braking Start Frequency
Sets the frequency at which DC Injection Braking starts when Ramp to Stop
(b1-03 = 0) is selected. If b2-01< E1-09, DC Injection Braking starts at E1-09.
0.0 to 10.0 0.5 Hz A A A 189 —
b2-02 DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the drive rated current. 0 to 75 50% A A − 18A —
b2-03
DC Injection Braking Time/DC
Excitation Time at Start
Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds. 0.00 to 10.00
0.00 s
<1>
A A − 18B —
b2-04 DC Injection Braking Time at Stop
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is calculated as follows:
(b2-04) x 10 x (Output Freq) / (E1-04).
When b1-03 = 0, this parameter sets the amount of DC Injection time applied to
the motor at the end of the decel ramp or High Slip Braking.
Disabled when set to 0.00.
0.00 to 10.00 0.50 s A A − 18C —
b2-08
Magnetic Flux Compensation
Capacity
Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).
0 to 1000 0% − A − 190 —
b2-12 Short Circuit Brake Time at Start
Sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00.
<32>
0.00 to 25.50 0.00 s − − A 1BA —
b2-13 Short Circuit Brake Time at Stop
Sets Short-Circuit Brake operation time at stop. Used to stop a motor rotating due
to inertia. Disabled when set to 0.00 seconds.
<32>
0.00 to 25.50 0.50 s − − A 1BB —
b3: Speed Search
Use B3 parameters to configure Speed Search function operation.
b3-01 Speed Search Selection
Enables/disables speed search function at start.0: Disabled - Speed Search is not
automatically performed at start.
1: Enabled - Speed Search is automatically performed at start.
0 to 1 0 A A A 191 —
b3-02 Speed Search Deactivation Current
Sets the current level at which the speed is assumed to be detected and Speed
Search is ended. Set in percent of the drive rated current.
0 to 200
120 <2>
A A − 192 —
b3-03 Speed Search Deceleration Time
Sets the time constant used to reduce the output frequency during speed search.
Related to a change from max. output frequency to 0.
0.1 to 10.0 2.0 s A A − 193 —
b3-05 Speed Search Delay Time
Delays the speed search operation after a momentary power loss to allow time
for an external output contactor to close.
0.0 to 100 0.2 s A A A 195 —
b3-06 Output Current 1 during Speed Search
Sets the current injected to the motor at the beginning of Estimation type Speed
Search. Set as a factor to the motor rated current.
0.0 to 2.0 <12> A A − 196 —
b3-10
Speed Search Detection Compensation
Gain
Sets the gain which is applied to the speed detected by Speed Estimation Speed
Search before the motor is reaccelerated. Increase this setting if OV occurs when
performing speed search.
1.00 to 1.20 1.05 A A − 19A —
b3-14 Bi-Directional Speed Search Selection
Selects if Speed Search detects the motor rotation direction during speed search.
0: Disabled–Frequency reference direction used
1: Enabled–Detected direction used
0, 1 0 A A − 19E —
b3-17 Speed Search Restart Current Level Sets the speed search restart current level in percentage of the drive rated current. 0 to 200 150% A A − 1F0 —
b3-18 Speed Search Restart Detection Time Sets the time in seconds for speed search restart to be detected. 0.00 to 1.00 0.10 s A A − 1F1 —
b3-19 Number of Speed Search Restarts Sets the number of restarts possible for speed search restart operations. 0 to 10 3 A A − 1F2 —
b3-24 Speed Search Method Selection
Sets the Speed Search detection mode.
0: Current Detection Type
1: Speed Estimation Type
0, 1 0 A A − 1C0 —
b3-25 Speed Search Retry Interval Time Sets the wait time before Speed Search restarts. 0 to 30.0 0.5 s A A A 1C8 —
B.2 Parameter Table
296