EasyManuals Logo

YASKAWA V1000 Series Technical Manual

YASKAWA V1000 Series
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
No. Parameter Name No. Parameter Name
b6-02 Dwell Time at Start H2-01 Terminals MA, MB, and MC Function Selection
C1-01 Acceleration Time 1 L1-01 Motor Overload Protection Selection
C1-02 Deceleration Time 1 L4-01 Speed Agreement Detection Level
C6-02 Carrier Frequency Selection L6-02 Torque Detection Level 1
d1-01 Frequency Reference 1 L6-03 Torque Detection Time 1
Note: Read the instructions listed in Hoist Application Preset Specifics on page 73 when using Hoist Application Preset.
Table 4.17 Crane Application (Travel): Parameters and Settings
No. Parameter Name Optimum Setting
A1-02 Control Mode 0: V/f control
b1-01 Frequency Reference Selection 0: Operator
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Duty Cycle 0: Heavy Duty
C6-02 Carrier Frequency Selection 2: 5 kHz
d1-01 Frequency Reference 1 6.0 Hz
d1-02 Frequency Reference 2 30.0 Hz
d1-03 Frequency Reference 3 60.0 Hz
H1-05 Multi-Function Digital Input Terminal S5 Function 3: Multi-Step Speed 1
H1-06 Multi-Function Digital Input Terminal S6 Function 4: Multi-Step Speed 2
H2-02 Terminals P1 Function Selection (open-collector) 37: During frequency output
L3-04 Stall Prevention Selection during Decel 0: Disabled
L8-05 Input Phase Loss Protection Selection 1: Enabled
L8-07 Output Phase Loss Protection 1: Triggered when a single phase is lost
L8-38 Carrier Frequency Reduction 1: Always derated
L8-41 Current Alarm Selection 1: Enabled (alarm output)
Table 4.18 Parameters Automatically Saved as Preferred (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection d1-03 Frequency Reference 3
C1-01 Acceleration Time 1 E2-01 Motor Rated Current
C1-02 Deceleration Time 1 H1-05 Multi-Function Digital Input Terminal S5 Function
C6-02 Carrier Frequency Selection H1-06 Multi-Function Digital Input Terminal S6 Function
d1-01 Frequency Reference 1 H2-01 Terminals MA, MB, and MC Function Selection
d1-02 Frequency Reference 2 L1-01 Motor Overload Protection Selection
Note: A sequence to release the brake is needed when the multi-function output photocoupler P2-PC closes. Refer to Hoist Application Preset Specifics on page 73 for more
information.
n
Hoist Application Preset Specifics
This section lists some important points when using the Hoist Application Preset (A1-06 = 6).
Conditions for Opening and Closing the Holding Brake
Use an output signal as described below to operate the holding brake in a hoist application.
Make sure that frequency detection is set so that it does not operate during baseblock (L4-07 = “0”). Even when an external baseblock command is present,
the output frequency will rise when a run command is entered. If frequency detection were to be enabled during baseblock, (i.e., L4-07 = 1) then the brake
would be improperly released. To activate and release the brake using the multi-function output terminals P2-PC, program the drive as shown in the table
below:
Brake Open/Close Brake Activation Level Control Mode
Function Parameter Signal Parameter V/f OLV OLV for PM
Frequency Detection 2
L4-07 = 0
H2-03 = 5
Frequency Detection Level Frequency Detection
Width
L4-01 = 1.0 to 3.0 Hz <1>
L4-02 = 0.0 to 0.5 Hz <2>
O O -
<1> This setting range is available when using OLV Control. In V/f Control, set the level as the motor rated slip frequency pulse 0.5 Hz. Not enough motor torque will be created if this value is
set too low, and the load may tend to slip. Make sure this value greater than the minimum output frequency and greater than the value of L4-02 as shown in the diagram below. If this value
is set too high, there may be a jolt at start.
<2> Adjust Hysteresis for Frequency Detection 2 by changing the frequency detection width (L4-02) between 0.0 and 0.5 Hz. If the load slips during stop, make incremental changes of 0.1 Hz
until the load no longer slips.
L4-02
L4-01
OFF
ON
Output
Frequency
Frequency
Detection 2
Time
Sequence Circuit Design for Opening and Closing the Holding Brake
Design the braking sequence as follows:
The brake should release when terminal P2-PC closes in response to the run conditions on the sequence side.
When a fault signal is output, the brake should close. When an up or down command is entered, the brake should release.
4.5 Application Presets
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
73
4
Start-Up Programming
& Operation

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled

Related product manuals