Table 15: Ethernet rear port settings
Parameter Values (Range) Unit Step Default Description
IP address 192.168.2.10 IP address for rear port(s)
Subnet mask 255.255.255.0 Subnet mask for rear port(s)
Default gateway 192.168.2.1 Default gateway for rear port(s)
Mac address XX-XX-XX-XX-
XX-XX
Mac address for rear port(s)
Table 16: General system settings
Parameter Values (Range) Unit Step Default Description
Rated frequency 1=50Hz
2=60Hz
1=50Hz Rated frequency of the network
Phase rotation 1=ABC
2=ACB
1=ABC Phase rotation order
Blocking mode 1=Freeze timer
2=Block all
3=Block TRIP
output
1=Freeze timer Behavior for function BLOCK inputs
Bay name
1)
REF615
2)
Bay name in system
IDMT Sat point 10...50 I/I> 1 50 Overcurrent IDMT saturation point
Frequency adaptivity
3)
0=Disable
1=Enable
0=Disable Enabling frequency adaptivity
SMV Max Delay 0=1.90 1.58 ms
1=3.15 2.62 ms
2=4.40 3.67 ms
3=5.65 4.71 ms
4=6.90 5.75 ms
1=3.15 2.62 ms SMV Maximum allowed delay
1) Used in the protection relay main menu header and as part of the disturbance recording identification
2) Depending on the product variant
3) Available only in REG615
Table 17: HMI settings
Parameter
Values (Range) Unit Step Default Description
FB naming convention 1=IEC61850
2=IEC60617
3=IEC-ANSI
1=IEC61850 FB naming convention used in IED
Default view 1=Measurements
2=Main menu
3=SLD page 1
1=Measurements LHMI default view
Backlight timeout 1...60 min 1 3 LHMI backlight timeout
Web HMI mode 1=Active read only
2=Active
3=Disabled
3=Disabled Web HMI functionality
Table continues on next page
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 63