Parameter Values (Range) Unit Step Default Description
Web HMI timeout 1...60 min 1 3 Web HMI login timeout
SLD symbol format 1=IEC
2=ANSI
1=IEC Single Line Diagram symbol format
Autoscroll delay 0...30 s 1 0 Autoscroll delay for Measurements view
Setting visibility 1=Basic
2=Advanced
1=Basic Setting visibility for HMI
Table 18: IEC 61850-8-1 MMS settings
Parameter Values (Range) Unit Step Default Description
Unit mode
1=Primary
1)
0=Nominal
2)
2=Primary-
Nominal
3)
0=Nominal IEC 61850-8-1 unit mode
1) MMS client expects primary values from event reporting and data attribute reads
2) MMS client expects nominal values from event reporting and data attribute reads; this is the default for PCM600
3) For PCM600 use only, When Unit mode is set to "Primary", the PCM600 client can force its session to "Nominal" by selecting "Primary-Nominal"
and thus parameterizing in native form. The selection is not stored and is therefore effective only for one session. This value has no effect if
selected via the LHMI.
Table 19: Modbus settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
5=disable Enable or disable this protocol instance
Port 1=COM 1
2=COM 2
3=Ethernet - TCP 1
3=Ethernet - TCP
1
Port selection for this protocol instance. Select
between serial and Ethernet based
communication.
Mapping selection
1...2 1 1 Chooses which mapping scheme will be used
for this protocol instance.
Address 1...254 1 1 Unit address
Link mode 1=RTU
2=ASCII
1=RTU Selects between ASCII and RTU mode. For
TCP, this should always be RTU.
TCP port 1...65535 1 502 Defines the listening port for the Modbus TCP
server. Default = 502.
Parity 0=none
1=odd
2=even
2=even Parity for the serial connection.
Start delay 0...20 1 4 Start delay in character times for serial
connection
End delay 0...20 1 4 End delay in character times for serial
connections
CRC order 0=Hi-Lo
1=Lo-Hi
0=Hi-Lo Selects between normal or swapped byte order
for checksum for serial connection. Default: Hi-
Lo.
Table continues on next page
Section 3 1MAC059074-MB A
Basic functions
64 615 series ANSI
Technical Manual