Parameter Values (Range) Unit Step Default Description
UR Class 1 Min events 0...999 1 2 Min number of class 1 events to generate UR
UR Class 1 TO 0...65535 ms 1 50 Max holding time for class 1 events to generate
UR
UR Class 2 Min events 0...999 1 2 Min number of class 2 events to generate UR
UR Class 2 TO 0...65535 ms 1 50 Max holding time for class 2 events to generate
UR
UR Class 3 Min events 0...999 1 2 Min number of class 3 events to generate UR
UR Class 3 TO 0...65535 ms 1 50 Max holding time for class 3 events to generate
UR
Legacy master UR 1=Disable
2=Enable
1=Disable Legacy DNP master unsolicited mode support.
When enabled relay does not send initial
unsolicited message.
Legacy master SBO
1=Disable
2=Enable
1=Disable Legacy DNP Master SBO sequence number
relax enable
Default Var Obj 01 1=1:BI
2=2:BI&status
1=1:BI 1=BI; 2=BI with status.
Default Var Obj 02 1=1:BI event
2=2:BI event&time
2=2:BI event&time 1=BI event; 2=BI event with time.
Default Var Obj 03 1=1:DBI
2=2:DBI&status
1=1:DBI 1=DBI; 2=DBI with status.
Default Var Obj 04 1=1:DBI event
2=2:DBI
event&time
2=2:DBI
event&time
1=DBI event; 2=DBI event with time.
Default Var Obj 20 1=1:32bit Cnt
2=2:16bit Cnt
5=5:32bit Cnt
noflag
6=6:16bit Cnt
noflag
2=2:16bit Cnt 1=32 bit counter; 2=16 bit counter; 5=32 bit
counter without flag; 6=16 bit counter without
flag.
Default Var Obj 21
1=1:32bit FrzCnt
2=2:16bit FrzCnt
5=5:32bit
FrzCnt&time
6=6:16bit
FrzCnt&time
9=9:32bit FrzCnt
noflag
10=10:16bit FrzCnt
noflag
6=6:16bit
FrzCnt&time
1=32 bit frz counter; 2=16 bit frz counter; 5=32
bit frz counter with time; 6=16 bit frz counter
with time; 9=32 bit frz counter without flag;
10=16 bit frz counter without flag.
Default Var Obj 22
1=1:32bit Cnt evt
2=2:16bit Cnt evt
5=5:32bit Cnt
evt&time
6=6:16bit Cnt
evt&time
6=6:16bit Cnt
evt&time
1=32 bit counter event; 2=16 bit counter event;
5=32 bit counter event with time; 6=16 bit
counter event with time.
Table continues on next page
1MAC059074-MB A Section 3
Basic functions
615 series ANSI 67
Technical Manual