Table 20: DNP3 settings
Parameter Values (Range) Unit Step Default Description
Operation 1=enable
5=disable
5=disable Operation Disable / Enable
Port 1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet TCP
+UDP 1
3=Ethernet - TCP
1
Communication interface selection
Unit address 1...65519 1 1 DNP unit address
Master address 1...65519 1 3 DNP master and UR address
Mapping select 1...2 1 1 Mapping select
ClientIP 0.0.0.0 IP address of client
TCP port 20000...65535 1 20000 TCP Port used on ethernet communication
TCP write authority 0=No clients
1=Reg. clients
2=All clients
2=All clients 0=no client controls allowed; 1=Controls
allowed by registered clients; 2=Controls
allowed by all clients
Link keep-alive
0...65535 s 1 0 Link keep-alive interval for DNP
Validate master addr 1=Disable
2=Enable
1=Disable Validate master address on receive
Self address 1=Disable
2=Enable
2=Enable Support self address query function
Need time interval 0...65535 min 1 30 Period to set IIN need time bit
Time format 0=UTC
1=Local
1=Local UTC or local. Coordinate with master.
CROB select timeout 1...65535 s 1 10 Control Relay Output Block select timeout
Data link confirm 0=Never
1=Only Multiframe
2=Always
0=Never Data link confirm mode
Data link confirm TO 100...65535 ms 1 3000 Data link confirm timeout
Data link retries 0...65535 1 3 Data link retries count
Data link Rx to Tx delay 0...255 ms 1 0 Turnaround transmission delay
Data link inter char delay 0...20 char 1 4 Inter character delay for incoming messages
App layer confirm 1=Disable
2=Enable
1=Disable Application layer confirm mode
App confirm TO 100...65535 ms 1 5000 Application layer confirm and UR timeout
App layer fragment 256...2048 bytes 1 2048 Application layer fragment size
UR mode 1=Disable
2=Enable
1=Disable Unsolicited responses mode
UR retries 0...65535 1 3 Unsolicited retries before switching to UR
offline mode
UR TO 0...65535 ms 1 5000 Unsolicited response timeout
UR offline interval 0...65535 min 1 15 Unsolicited offline interval