Name Type Default Description
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
AU_OPEN BOOLEAN 0=False
Auxiliary open
1)
AU_CLOSE BOOLEAN 0=False
Auxiliary close
1)2)
TRIP BOOLEAN 0=False Trip signal
SYNC_OK BOOLEAN 1=True Synchronism-check OK
SYNC_ITL_BYP BOOLEAN 0=False Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
1) Not available for monitoring
2) Always direct operation
Table 864: 29DS Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False Apparatus open position
POSCLOSE BOOLEAN 0=False Apparatus close position
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
AU_OPEN BOOLEAN 0=False
Executes the command for open direction
1)2)
AU_CLOSE BOOLEAN 0=False
Executes the command for close direction
1)2)
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
1) Not available for monitoring
2) Always direct operation
Table 865: 29GS Input signals
Name
Type Default Description
POSOPEN BOOLEAN 0=False Apparatus open position
POSCLOSE BOOLEAN 0=False Apparatus close position
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
Table continues on next page