Description JPDE-[ ] DC Voltage Gnd fdbk mag (JD1/JPS1/JPS2 connector) out of range.
Possible Cause
The 24/48 V dc ground feedback magnitude is greater than Gnd_Mag_Trig_Volt.
Gnd_Mag_Trig_Volt is set too low.
One side of the 24/48 V dc source voltage is grounded.
Solution
Verify that Gnd_Mag_Trig_Volt is set correctly.
Check the connections to the specified connector.
Verify the grounding of the dc input signals. Refer to the JPDE help documentation.
If 24/48 VDC input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to Disabled.
152, 160
Description JPDE-[ ] fuse FU11/FU12 (JS1 connector) is blown or SWS1 switched OFF.
Possible Cause
The SWS1 is turned off and FuseDiag is enabled.
The FU11 or FU12 fuse is blown.
The 24/48 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 24/48 V dc input connections to the terminal board.
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to Disabled.