Description JPDE-[ ] fuse FU21/FU22 (JS2 connector) is blown or SWS2 switched OFF.
Possible Cause
The SWS2 is turned off and FuseDiag is enabled.
The FU21 or FU22 fuse is blown.
The 24/48 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 24/48 V dc input connections to the terminal board.
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to Disabled.
154, 162
Description JPDE-[ ] fuse FU31/FU32 (JS3 connector) is blown or SWS3 switched OFF.
Possible Cause
The SWS3 is turned off and FuseDiag is enabled.
The FU31 or FU32 fuse is blown.
The 24/48 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 24/48 V dc input connections to the terminal board.
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to Disabled.