Address Designaon Default seng Data type Factor A M
0x243C:001 Device: Ethernet commands: Device: Start rmware
update
O/Ready [0] U8 CX
0x2450 Engineering port control No acon/No error [0] U8 X
0x2451:001 Engineering port sengs: IP address 0.0.0.0 U32 E
0x2451:002 Engineering port sengs: Subnet 0.0.0.0 U32 E
0x2451:003 Engineering port sengs: Gateway 0.0.0.0 U32 E
0x2451:004 Engineering port sengs: DHCP Enabled [1] U8 -
0x2452:001 Acve engineering port sengs: IP address - (Read only) U32 EX
0x2452:002 Acve engineering port sengs: Subnet - (Read only) U32 EX
0x2452:003 Acve engineering port sengs: Gateway - (Read only) U32 EX
0x2452:005 Acve engineering port sengs: MAC address - (Read only) OCTET[6] X
0x245A:001 NTP server addresses: Acvate NTP server
addr
esses
No acon/no error [0] U8 X
0x245A:002 NTP server addresses: NTP server address 1 0.0.0.0 U32 E
0x245A:003 NTP server addresses: NTP server address 2 0.0.0.0 U32 E
0x245A:004 NTP server addresses: NTP server address 3 0.0.0.0 U32 E
0x245A:005 NTP server addresses: NTP server address 4 0.0.0.0 U32 E
0x245B:001 System me: Time base NTP [0] U8 X
0x245B:002 System me: Current me ns U64 1 TX
0x2500 Touch probe lter me 0 us U16 1 -
0x2539:001 Hardware-Diagnose: 24 V supply actual voltage x.x V (Read only) U16 10 X
0x2539:002 Hardware-Diagnose: Control board temperature x.x °C (Read only) I16 10 X
0x2540:001 Mains sengs: Rated mains voltage 400 Ve [1] U8 -
0x2540:002 Mains sengs: Undervoltage warning threshold 430 V U16 1 -
0x2540:003 Mains sengs: Undervoltage error threshold x V (Read only) U16 1 -
0x2540:004 Mains sengs: Undervoltage reset threshold x V (Read only) U16 1 -
0x2540:005 Mains sengs: Overvoltage warning threshold 795 V U16 1 -
0x2540:006 Mains sengs: Overvoltage error threshold x V (Read only) U16 1 -
0x2540:007 Mains sengs: Overvoltage reset threshold x V (Read only) U16 1 -
0x2540:008 Mains sengs: DC link voltage crical - (Read only) U8 1 X
0x2541:003 Brake energy management: Reduced threshold 0 V U16 1 -
0x2550:001 Brake resistor: Minimum resistance x.x Ω (Read only) U16 10 X
0x2550:002 Brake resistor: Resistance value 180.0 Ω U16 10 -
0x2550:003 Brake resistor: Rated power 5600 W U32 1 -
0x2550:004 Brake resistor: Maximum thermal load 485 kWs U32 1 -
0x2550:006 Brake resistor: Reference resistance Minimum resistance [0] U8 -
0x2550:007 Brake resistor: Thermal load x.x % (Read only) U16 10 X
0x2550:008 Brake resistor: Warning threshold 90.0 % U16 10 -
0x2550:010 Brake resistor: Response to warning Warning [2] U8 -
0x2550:011 Brake resistor: Response to error No response [0] U8 -
0x2580:001 Distributed Clocks : Real me status - (Read only) U8 X
0x2580:002 Distributed Clocks : First seng
me x ns (Read only) U64 1 TX
0x2580:003 Distributed Clocks : Newest seng
me x ns (Read only) U64 1 TX
0x2580:004 Distributed Clocks : Current me x ns (Read only) U64 1 TX
0x2590:003 Energy saving: State of actual energy saving mode - (Read only) U8 HX
0x261C:001 Favorites
sengs: Parameter 1 U32 1 -
0x261C:002 Favorites sengs: Parameter 2 U32 1 -
0x261C:003 Favorites sengs: Parameter 3 U32 1 -
0x261C:004 Favorites sengs: Parameter 4 U32 1 -
0x261C:005 Favorites sengs: Parameter 5 U32 1 -
0x261C:006 Favorites sengs: Parameter 6 U32 1 -
0x261C:007 Favorites
sengs: Parameter 7 U32 1 -
0x261C:008 Favorites sengs: Parameter 8 U32 1 -
0x261C:009 Favorites sengs: Parameter 9 U32 1 -