Technology instructions
10.3 Motion control
S7-1200 Programmable controller
780 System Manual, V4.2, 09/2016, A5E02486680-AK
ErrorID
ErrorInfo
Description
Remedy
16#8410
Invalid value at parameter "Parameter" of the motion control instruction
16#0002 Value is not a valid number Correct the value; restart the command.
16#000B Address is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#0028 Data type of VARIANT pointer "Parameter"
and "Value" do not match.
Use a suitable data type; restart command.
16#0029 VARIANT pointer "Parameter" does not point
to a data block of the technology object.
Correct the VARIANT pointer; restart the com-
mand.
16#002A The value at the VARIANT pointer "Parameter"
cannot be read.
Correct the VARIANT pointer; restart the com-
mand.
16#002B
The value at the VARIANT pointer "Parameter"
cannot be written.
Correct the VARIANT pointer or value; restart the
command.
16#002C
The axis is not disabled.
Disable the axis; restart the command.
16#8411
Invalid value at parameter "Value" of the motion control instruction
16#0002
Value is not a valid number
Correct the value; restart the command.
Configuration error of the axis
ErrorID
ErrorInfo
Description
Remedy
16#8600
Parameter assignment of pulse generator (PTO is invalid
16#000B
The address is invalid
Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#0014 The selected hardware is used by another
application
16#8601
Parameter assignment of the high-speed counter (HSC) is invalid
16#000B The address is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#0014 The selected hardware is used by another
application
16#8602
Invalid parameter assignment of "Enable output"
16#000B The address is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#8603
Invalid parameter assignment of "Ready input"
16#000B The address is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#8604
Invalid "Pulses per motor revolution" value
16#000A Value is less than or equal to zero Download error-
free configuration to the controller;
enable the axis again with instruction
"MC_Power".