Technology instructions
10.3 Motion control
S7-1200 Programmable controller
System Manual, V4.2, 09/2016, A5E02486680-AK
783
ErrorID
ErrorInfo
Description
Remedy
16#860C
Value for position of the high SW limit switch is invalid
16#0002 Value is not a valid number
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#0005 Value is outside the number range (greater
than 1E+12)
16#0006 Value is outside the number range (less than
1E+12)
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#860D
Invalid address of the low HW limit switch
16#000B
Invalid address
Download error-free configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#000C The address of the falling edge is invalid
16#000D
The address of the rising edge is invalid
16#860E
Invalid address of the high HW limit switch
16#000B
Invalid address
Download error-fr
ee configuration to the controller;
enable the axis again with instruction
"MC_Power".
16#000C
The address of the falling edge is invalid
16#000D
The address of the rising edge is invalid
16#860F
Invalid "home position offset" value
16#0002
Value is not a valid number
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
16#0005 Value is outside the number range (greater
than 1E+12)
16#0006 Value is outside the number range (less than
1E+12)
16#0030 Value has an incorrect number format or is
outside the valid number range
Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.