The configuration for the resolution of the linear encoder is faulty. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.Resolution
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
The set fine resolution for Gn_XIST1 is invalid. Invalid value in <Axis
name>.Sensor.Sensor[1].Parameter.FineResolutionXist1
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
The set fine resolution for Gn_XIST1 in <Axis
name>.Sensor.Sensor[1].Parameter.FineResolutionXist1 is not consistent with the setting in
PROFIdrive parameter P979
16#0030 Value has an incorrect number format or is
outside the valid number range
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"
and restart the command, if necessary.
Invalid value for the configuration date <Axis name>.Actor.Interface.AddressIn or <Axis
name>.Actor.Interface.AddressOut
16#0011 The selection value is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
The value set in the tag <Axis name>.Sensor.Sensor[1].Type is invalid.
16#0011 The selection value is invalid Download error-
free configuration to the controller;
enable the axis again with instruction
The set encoder system is invalid. Invalid value in <Axis name>.Sensor.Sensor[1].System
16#0011 The selection value is invalid
• Download error-free configuration to the con-
troller; enable the axis again with instruction
"MC_Power".
• Correct the incorrect value online;
acknowledge error with instruction "MC_Reset"