Technology instructions
10.3 Motion control
S7-1200 Programmable controller
794 System Manual, V4.2, 09/2016, A5E02486680-AK
ErrorID
ErrorInfo
Description
Remedy
Error reaction
16#8041
Errors when adapting the encoder configuration
16#0030 Value has the wrong numerical for-
mat or is outside the valid number
range.
Restart Adaptation Error
16#005A Adaptation was cancelled because of
a lack of resources.
Restart Adaptation Error
16#005B Adaptation is possible only if the
device was wired directly to an IO
area.
Restart Adaptation Error
16#0059 The device is not assigned to any
SINAMICS drive unit or does not
support the services necessary for
adaptation.
Restart Adaptation Error
16#0062 Encoder System (r0979[1/11].0): A
parameter does not exist or its value
cannot be read or is outside the per-
mitted limits. Reading the parameters
was cancelled because of an error
indicated by the hardware.
Restart Adaptation Error
16#0063 Encoder resolution (r0979[2/12]): A
parameter does not exist or its value
cannot be read or is outside the per-
mitted limits. Reading the parameters
was cancelled because of an error
indicated by the hardware.
Restart Adaptation Error
16#0064 Encoder resolution Gx_XIST1
(r0979[3/13]): A parameter does not
exist or its value cannot be read or is
outside the permitted limits. Reading
the parameters was cancelled be-
cause of an error indicated by the
hardware.
Restart Adaptation Error
16#0065 Encoder resolution Gx_XIST2
(r0979[4/14]): A parameter does not
exist or its value cannot be read or is
outside the permitted limits. Reading
the parameters was cancelled be-
cause of an error indicated by the
hardware.
Restart Adaptation Error
16#0066 Number of resolvable encoder revolu-
tions (r0979[5/15]): A parameter does
not exist or its value cannot be read
or is outside the permitted limits.
Reading the parameters was can-
celled because of an error indicated
by the hardware.
Restart Adaptation Error