7. MAINTENANCE
Code Enumerable Description
00
INITIALIZING
This state is presented while other states are not ready.
01
RESET_WATCHDOG
Application in Stop Mode due to hardware watchdog re-
set or runtime reset, when the option “Start User Appli-
cation After a Watchdog Reset” is unmarked.
02
ABSENT_MODULES_HOT_SWAP_
DISABLED
Application in Stop Mode due to Absent Modules diag-
nostic being set when the Hot Swap Mode is "Disabled"
or "Disabled, for declared modules only".
03
CFG_MISMATCH_HOT_SWAP_
DISABLED
Application in Stop Mode due to Configuration Mis-
match diagnostic being set when the Hot Swap Mode is
"Disabled" or "Disabled, for declared modules only".
04
ABSENT_MODULES_HOT_SWAP_
STARTUP_CONSISTENCY
Application in Stop Mode due to Absent Modules diag-
nostic being set when the Hot Swap Mode is "Enabled,
with startup consistency" or "Enabled, with startup con-
sistency for declared modules only".
05
CFG_MISMATCH_HOT_SWAP_
STARTUP_CONSISTENCY
Application in Stop Mode due to Incompatible Config-
uration diagnostic being set when the Hot Swap Mode
is "Enabled, with startup consistency" or "Enabled, with
startup consistency for declared modules only".
06
APPL_STOP_ALLOWED_TO_RUN
Application in Stop Mode and all consistencies executed
successfully. The application can be set to Run Mode.
07
APPL_STOP_MODULES_NOT_READY
Application in Stop Mode and all consistencies executed
successfully, but the I/O modules are not able to start the
system. It is not possible to set the application to Run
Mode.
08
APPL_STOP_MODULES_GETTING_
READY_TO_RUN
Application in Stop Mode and all consistencies executed
successfully. The I/O modules are being prepared to start
the system. It is not possible to set the application to Run
Mode.
09
NORMAL_OPERATING_STATE
Application in Run Mode.
10
MODULE_CONSISTENCY_OK
Internal usage.
11
APPL_STOP_DUE_TO_EXCEPTION
Application in Stop Mode due to an exception in the
CPU.
12
DUPLICATED_SLOT_HOT_SWAP_
DISABLED
Application in Stop Mode due to Duplicated Slots diag-
nostic being set when the Hot Swap Mode is "Disabled"
or "Disabled, for declared modules only".
13
DUPLICATED_SLOT_HOT_SWAP_
STARTUP_CONSISTENCY
Application in Stop Mode due to Duplicated Slots diag-
nostic being set when the Hot Swap Mode is "Enabled,
with startup consistency" or "Enabled, with startup con-
sistency for declared modules only".
14
DUPLICATED_SLOT_HOT_SWAP_
ENABLED
Application in Stop Mode due to Duplicated Slots diag-
nostic being set when the Hot Swap Mode is "Enabled,
without startup consistency".
15
NON_DECLARED_MODULE_HOT_
SWAP_STARTUP_CONSISTENCY
Application in Stop Mode due to Non Declared Modules
diagnostic being set when the Hot Swap Mode is "En-
abled, with startup consistency".
16
NON_DECLARED_MODULE_HOT_
SWAP_DISABLED
Application in Stop Mode due to Non Declared Modules
diagnostic being set when the Hot Swap Mode is "Dis-
abled".
Table 238: Codes of the Situations in which the Application Stops
368

Table of Contents

Other manuals for ALTUS Nexto Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ALTUS Nexto Series and is the answer not in the manual?

ALTUS Nexto Series Specifications

General IconGeneral
BrandALTUS
ModelNexto Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals