2. TECHNICAL DESCRIPTION
2.2.3. Protocols
NX3030 Interface
Open Protocol Yes COM1 / COM2
MODBUS RTU Master Yes COM1 / COM2
MODBUS RTU Slave Yes COM1 / COM2
MODBUS TCP Client Yes NET1 / NET2
MODBUS TCP Server Yes NET1 / NET2
MODBUS RTU over TCP Client Yes NET1 / NET2
MODBUS RTU over TCP Server Yes NET1 / NET2
CANopen Master No -
CANopen Slave No -
CAN low level No -
SAE J-1939 No -
OPC DA Server Yes NET1 / NET2
OPC UA Server Yes NET1 / NET2
EtherCAT Master Yes NET1 / NET2
SNMP Agent Yes NET1 / NET2
DNP3 Server (Event-oriented data) Yes NET1 / NET2
IEC 60870-5-104 Server Yes NET1 / NET2
EtherNet/IP Scanner Yes NET1 / NET2
EtherNet/IP Adapter Yes NET1 / NET2
MQTT Client Yes NET1 / NET2
SNTP Client (for clock synchronism) Yes NET1 / NET2
PROFINET Controller Yes NET1 / NET2
PROFINET Device No -
Table 9: Protocols
Note:
PROFINET Controller: Enabled for use on a simple (not ring) network with up to 8 devices. For larger applications,
consult technical support.
2.2.4. Serial Interfaces
2.2.4.1. COM 1
COM 1
Connector Shielded female DB9
Physical interface RS-232C
Modem signals RTS, CTS, DCD
Baud rate
200, 300, 600, 1200, 1800, 2400, 4800, 9600, 19200, 38400,
57600, 115200 bps
Isolation
Logic to Serial Port Not isolated
Serial Port to protection
earth
1000 Vac / 1 minute
Table 10: COM 1 Serial Interface Features
12