EasyManua.ls Logo

ALTUS Nexto Series

ALTUS Nexto Series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. INSTALLATION
Figure 9: RS-485 Connections without Termination Diagram
Diagram Note:
1. The not connected terminals must be insulated so they do not make contact with each other.
3.5.2. RS-485 Communication with Internal Termination
In order to connect in a RS-485 network using the internal termination, the cable AL-1763 identified terminals must be
connected in the respective device terminals, as shown on table below.
AL-1763 terminals CPU terminal signals
0 Shield
1 D+
2 D+
3 D+
4 Not connected
5 Not connected
6 D-
7 D-
8 D-
Table 26: RS-485 Connections with Internal Termination
PS.: The internal termination available is a safe state type in open mode.
The figure diagram below indicates how the AL-1763 connection terminals should be connected in the device terminals.
Figure 10: RS-485 Connections with Internal Termination Diagram
Diagram Note:
25

Table of Contents

Other manuals for ALTUS Nexto Series

Related product manuals