High-Speed Input and
Pulse Output Features
3–51
High-Speed Input and Pulse Output Features
The following program selects Mode 50, then programs the pulse catch code for X0.
Inputs X1 and X2 are configured as filtered inputs with 10 and 30 mS time constants
respectively. The program is otherwise generic, and may be adapted to your
application.
SP0
LD
K50
Load constant K50 into the accumulator. This
selects Mode 50 as the HSIO mode.
OUT
V7633
Output this constant to V7633, the location of the
HSIO Mode select register.
DirectSOFT
Mode 50
LD
K1006
Load the constant K1006 which is required to select
filtered inputs with a 10 mS filter time constant.
OUT
V7635
Output this constant to V7635, configuring X1.
Filtered Inputs
OUT
V7636
Output this constant to V7636, configuring X2.
LD
K5
Load the constant K5 which is required to configure X0
as the pulse catch input.
OUT
V7634
Output this constant to V7634, configuring the pulse
catch option for X0.
Pulse Catch
END
END coil marks the end of the main program..
Main Program
Use the pulse catch input to set output Y0 on. This will
work even for a very short pulse on X0.
LD
K3006
Load the constant K3006 which is required to select
filtered inputs with a 30 mS filter time constant.
X0
SET
Y0
Pulse Catch
Program Example

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DL05 and is the answer not in the manual?

Automationdirect.com DL05 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDL05
CategoryController
LanguageEnglish

Related product manuals