Installation, Wiring,
and Specifications
2–27
Installation, Wiring, and Specifications
The six relay output channels use terminals on the right side of the connector.
Outputs are organized into two banks of three normally-open relay contacts. Each
bank has a common terminal. The wiring example on the last page shows all
commons connected together, but separate supplies and common circuits may be
used. The equivalent output circuit shows one channel of a typical bank. The relay
contacts can switch AC or DC voltages.
External Power Requirements 95 – 240 VAC, 30 VA maximum,
Communication Port 1
9600 baud (Fixed), 8 data bits, 1 stop bit,
odd parity
K–Sequence (Slave)
DirectNET (Slave)
MODBUS (Slave)
Communication Port 2
9600 baud (default), 8 data bits, 1 stop bit,
odd parity
K–Sequence (Slave)
DirectNET (Master/Slave)
MODBUS (Master/Slave)
Non-sequence / print
Programming cable type D2–DSCBL
Operating Temperature
32 to 131° F (0 to 55_ C)
Storage Temperature
–4 to 158° F (–20 to 70_ C)
Relative Humidity 5 to 95% (non-condensing)
Environmental air No corrosive gases permitted
Vibration MIL STD 810C 514.2
Shock MIL STD 810C 516.2
Noise Immunity NEMA ICS3–304
Terminal Type Removable
Wire Gauge One AWG16 or two AWG18, AWG24 minimum
Input Voltage Range (Min. - Max.) 80 – 132 VAC, 47 - 63 Hz
Operating Voltage Range 90 – 120 VAC, 47 -63 Hz
Input Current 8 mA @ 100 VAC at 50 Hz
10 mA @ 100 VAC at 60 Hz
Max. Input Current 12 mA @ 132 VAC at 50 Hz
15 mA @ 132 VAC at 60 Hz
Input Impedance
14K @50 Hz, 12K @60 Hz
ON Current/Voltage >6 mA @ 75 VAC
OFF Current/Voltage <2 mA @ 20 VAC
OFF to ON Response < 40 mS
ON to OFF Response < 40 mS
Status Indicators Logic Side
Commons 4 channels / common x 2 banks
Output Voltage Range (Min. – Max.) 5 – 264 VAC (47 -63 Hz), 5 – 30 VDC
Operating Voltage Range 6 – 240 VAC (47 -63 Hz), 6 – 27 VDC
Output Current 2A / point, 6A / common
Max. leakage current 0.1 mA @264VAC
Smallest Recommended Load 5 mA @5 VDC
OFF to ON Response < 15 mS
ON to OFF Response < 10 mS
Status Indicators Logic Side
Commons 3 channels / common x 2 banks
Fuses None (external recommended)
D0–05AR
General
Specifications
AC Input
Specifications
X0 – X7
Relay Output
Specifications
Y0 – Y5

Table of Contents