Installation, Wiring,
and Specifications
2–29
Installation, Wiring, and Specifications
External Power Requirements 95 – 240 VAC, 30 VA maximum,
Communication Port 1
9600 baud (Fixed), 8 data bits, 1 stop bit,
odd parity
K–Sequence (Slave)
DirectNET (Slave)
MODBUS (Slave)
Communication Port 2
9600 baud (default), 8 data bits, 1 stop bit,
odd parity
K–Sequence (Slave)
DirectNET (Master/Slave)
MODBUS (Master/Slave)
Non-sequence / print
Programming cable type D2–DSCBL
Operating Temperature
32 to 131° F (0 to 55_ C)
Storage Temperature
–4 to 158° F (–20 to 70_ C)
Relative Humidity 5 to 95% (non-condensing)
Environmental air No corrosive gases permitted
Vibration MIL STD 810C 514.2
Shock MIL STD 810C 516.2
Noise Immunity NEMA ICS3–304
Terminal Type Removable
Wire Gauge One AWG16 or two AWG18, AWG24 minimum
Parameter High–Speed Inputs, X0 – X2 Standard DC Inputs X3 – X7
Min. - Max. Voltage Range 10.8 – 26.4 VDC 10.8 – 26.4 VDC
Operating Voltage Range 12 -24 VDC 12 -24 VDC
Peak Voltage 30 VDC (5 kHz maximum frequency) 30 VDC
Minimum Pulse Width
100 s
N/A
ON Voltage Level > 10 VDC > 10 VDC
OFF Voltage Level < 2.0 VDC < 2.0 VDC
Input Impedance
1.8 k @ 12 – 24 VDC 2.8 k @ 12 – 24 VDC
Max. Input Current 6mA @12VDC
13mA @24VDC
4mA @12VDC
8.5mA @24VDC
Minimum ON Current >5 mA >4 mA
Maximum OFF Current < 0.5 mA <0.5 mA
OFF to ON Response
<100 s
2 – 8 mS, 4 mS typical
ON to OFF Response
< 100 s
2 – 8 mS, 4 mS typical
Status Indicators Logic side Logic side
Commons 4 channels / common x 2 bank
Output Voltage Range (Min. - Max.) 5 -264 VAC (47 -63 Hz), 5 - 30 VDC
Operating Voltage 6 -240 VAC (47 -63 Hz), 6 - 27 VDC
Output Current 2A / point
6A / common
Maximum Voltage 264 VAC, 30 VDC
Max leakage current 0.1 mA @264 VAC
Smallest Recommended Load 5 mA
OFF to ON Response < 15 mS
ON to OFF Response < 10 mS
Status Indicators Logic Side
Commons 3 channels / common x 2 banks
Fuses None (external recommended)
D0–05DR
General
Specifications
DC Input
Specifications
Relay Output
Specifications