Input Specification
Inputs per module 4 (sink/source)
Operating voltage range 12–24 VDC
Input voltage range 10.8–26.4 VDC
Peak voltage 30.0 VDC
Maximum input current 11 mA @ 26.4 VDC
Input current Typical: 4 mA @ 12 VDC
8.5 mA @ 24 VDC
Input impedance 2.8k @ 12–24 VDC
ON voltage level > 10.0 VDC
OFF voltage level < 2.0 VDC
Minimum ON current 3.5 mA
Maximum OFF current 0.5 mA
ON to OFF response 2–8 ms, typical 4 ms
OFF to ON response 2–8 ms, typical 4 ms
Commons 1 (4 points / common)
Output Specification
Outputs per module 3
Operating voltage range 6–27 VDC / 6–240 VAC
Output type Relay, form A, SPST
Peak voltage 30.0 VDC/264 VAC
Maximum current (resistive) 1 A/point, 4 A/common
Minimum load current 5 mA @ 5 VDC
Maximum leakage current 0.1 mA @ 264 VAC
ON voltage drop N/A
Maximum inrush current Output: 3 A for 10 ms
Common: 10 A for 10 ms
OFF to ON response < 15 ms
ON to OFF response < 10 ms
Status indicators Module activity:
one green LED
Commons 1 (3 points/common)
Fuse N/A
Base power required (5 V) Max. 200 mA (all points ON)
Input Derating Chart
Equivalent input circuit
Equivalent output circuit
Output Derating Chart
0
10 20 30 40 50 55
Ambient Temperature (°C/°F)
32
50 68 86 104 122 131
C°
F°
0
10 20 30 40 50 55
Ambient Temperature (°C/°F)
32
50 68 86 104 122 131
C°
F°
Configuration shown is for current sinking
Note: The DL05 must have firmware version V4.10 (or later) for this module to function properly.

Table of Contents

Related product manuals