EasyManuals Logo

Automationdirect.com DL05 User Manual

Automationdirect.com DL05
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #356 background imageLoading...
Page #356 background image
PID Loop Operation
Maintenance
and Troubleshooting
8–12
PID Loop Operation
Each loop that you configure has the option of using a built-in Ramp/Soak generator
dedicated to that loop. This feature generates SP values that follow a profile. To use
the Ramp Soak feature, you must program a separate table of 32 words with
appropriate values. A DirectSOFT32 dialog box makes this easy to do.
In the loop table, the Ramp / Soak Table Pointer at Addr+34 must point to the start of
the ramp/soak data for that loop. This may be anywhere in user memory, and does
not have to adjoin to the Loop Parameter table, as shown to the left. Each R/S table
requires 32 words, regardless of the number of segments programmed.
The ramp/soak table parameters are defined in the table below. Further details are in
the section on Ramp / Soak Operation in this chapter.
Addr
Offset
Step Description Addr
Offset
Step Description
+ 00 1 Ramp End SP Value + 20 9 Ramp End SP Value
+ 01 1 Ramp Slope + 21 9 Ramp Slope
+ 02 2 Soak Duration + 22 10 Soak Duration
+ 03 2 Soak PV Deviation + 23 10 Soak PV Deviation
+ 04 3 Ramp End SP Value + 24 11 Ramp End SP Value
+ 05 3 Ramp Slope + 25 11 Ramp Slope
+ 06 4 Soak Duration + 26 12 Soak Duration
+ 07 4 Soak PV Deviation + 27 12 Soak PV Deviation
+ 10 5 Ramp End SP Value + 30 13 Ramp End SP Value
+ 11 5 Ramp Slope + 31 13 Ramp Slope
+ 12 6 Soak Duration + 32 14 Soak Duration
+ 13 6 Soak PV Deviation + 33 14 Soak PV Deviation
+ 14 7 Ramp End SP Value + 34 15 Ramp End SP Value
+ 15 7 Ramp Slope + 35 15 Ramp Slope
+ 16 8 Soak Duration + 36 16 Soak Duration
+ 17 8 Soak PV Deviation + 37 16 Soak PV Deviation
The individual bit definitions of the Ramp / Soak Table Programming Error Flags
word (Addr+35) is listed in the following table. Further details are given in the PID
Loop Mode section and in the PV Alarm section later in this chapter.
Bit R/S Error Flag Bit Description Read/
Write
Bit=0 Bit=1
0 Starting Addr out of lower V-memory range read – Error
1 Starting Addr out of upper V-memory range read – Error
2–3 Reserved for Future Use – – –
4 Starting Addr in System Parameter
V-memory Range
read – Error
5–15 Reserved for Future Use – – –
Ramp/Soak
Table Location
(Addr + 34)
V–Memory Space
User Data
LOOP #1
V2000
32 words
LOOP #2
32 words
V2037
Ramp/Soak #1
32 words
V3000
V2034 = 3000 Octal
Pointer to R/S table
Ramp/Soak Table
Programming Error
Flags
(Addr + 35)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com DL05 and is the answer not in the manual?

Automationdirect.com DL05 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelDL05
CategoryController
LanguageEnglish

Related product manuals