Getting Started
1–7
Getting Started
Step 2: Connect Switches to Input Terminals
To finish this quick-start exercise or study other examples in this manual, you’ll need
to connect some input switches as shown below. If you have DC inputs you will need
to use the FA–24PS (24VDC) or another external 12-24VDC power supply. Be sure
to follow the instructions in the accompanying WARNING note.
Toggle Switches, UL Listed
D0–05AR, D0–05AD, D0–05AA
(AC input versions, 120VAC only)
WARNING: DO NOT wire the
toggle switches as shown to
240VAC-powered units. The
discrete inputs will only accept
120VAC nominal. Also, remove
power and unplug the DL05 when
wiring the switches. Only use
UL-approved switches rated for at
least 250VAC, 1A for AC inputs.
Firmly mount the switches before
using.
D0–05DR, D0–05DD, D0–05DA
D0–05DR–D, D0–05DD–D
+
–
12–24VDC
Power Supply
Toggle Switches, UL Listed
(DC input versions, 12–24VDC)