Installation, Wiring,
and Specifications
2–5
Installation, Wiring, and Specifications
All of the terminals for the DL05 are contained on one connector block. In some
instances, it may be desireable to remove the connector block for easy wiring. The
connector is designed for easy removal with just a small screwdriver. The drawing
below shows the procedure for removal at one end.
Connector Removal
1. Loosen the retention screws on each end of the connector block.
2. From the center of the connector block, pry upward with the screwdriver
until the connector is loose.
The terminal block connector on DL05 PLCs have regular screw terminals, which
will accept either standard or #1 Philips screwdriver tips. You can insert one 16 AWG
wire under a terminal, or two 18 AWG wires (one on each side of the screw). Be
careful not to overtighten; maximum torque is 6 inch/ounces.
Spare terminal block connectors and connector covers may be ordered by individual
part numbers:
Part Number Qty Per Package Description
D0–IOCON 2
DL05 I/O Terminal Block
D0–IOCVR 2
DL05 I/O Terminal Cover
Connector
Removal