Equaon for calculang the reset me of the asynchronous motor
s× ×
t = »
s ss
n
s s
L 2 L
R R
Parameter Symbol Descripon Dimension unit
0x2942:001 V
p
Current controller gain V/A
- σ Leakage
- L
s
Motor stator inductance H
0x2C01:003 L
ss
Motor stator leakage inductance H
- T
Dead
me
Equivalent me constant for the
analog detecon and scanning =
0.00034 s
s
0x2942:002 T
n
Current controller reset me s
0x2C01:002 R
s
Motor stator resistance (value at
20° C)
Ω
Parameter
Address Name / seng range / [default seng] Info
0x2941 Current controller feedforward control Acvate/deacvate feedforward control.
Since the actuaon of the current controller is known, they can be pre-
c
ontrolled to increase the actuaons of the current controller.
Note!
For a feedforward control, the Motor equivalent circuit diagram data
must be known. If only esmated values are available, we recommend
you not to acvate the feedforward control.
0 Disable
1 Enable
0x2942:001 Current controller parameters: Gain
0.00 ... [148.21] ... 750.00 V/A
Gain factor Vp of the current controller.
0x2942:002 Current controller parameters: Reset me
0.01 ... [3.77] ... 2000.00 ms
Reset me Ti of the current controller.
0x2943 Current setpoint lter me
0.00 ... [0.00] ... 10.00 ms
Seng of the setpoint current lter me.