EasyManuals Logo

Lust MASTERCONTROL MC6000 Series User Manual

Default Icon
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
124 • Subject area _PMOD – Open-loop position control (option) Parameter Description MC6000/7000
_ENCD
_VAL
Index
_VFCON
_PMOD
_KPAD
Contents
Introduction
_SIO
_SCTY
_REF
_SYS
_IO1
_IO2
_CAN
_OPT1
_MOT
_CONF
_TCON
_SCON
_PCON
Example: POPRT = 0 Input port is IExx
POKPN = 72H IE01 = program bit 0
IE04 = program bit 1
IE05 = program bit 2
IE06 = program bit 3
537-POKTI - Configuration of table index (assignment of inputs, K03)
Example: POPRT = 0 Input port is IExx
POKTI = 34H IE02 = index bit 0
IE04 = index bit 1
IE05 = index bit 2
541-POKTP - Configuration of jog mode (assignment of inputs, K08)
Example: POPRT = 0 Input port is IExx
POKHE = 1004H IE02 -> positive jog input
IE04 -> negative jog input
Note:
With parameter 535-POPKD the type of coding is defined.
The parameter is only required for parameter setting via interface. In D
RIVEMANAGER
operation the value is calculated by way of the settings.
Function: Parameter only on MC7000.
POKTI defines which input bit is assigned to which bit of the table index. As a basic
rule, the least significant input bit influences bit 0 of the table index, the next signifi-
cant bit influences bit 1, etc.
Values:
Minimum Maximum Factory set. Unit MODE SMARTCARD Type
00H F0H 00H R1W4 POMOD USIGN8
Function: Parameter only on MC7000.
This parameter determines the assignment of jog mode inputs.
The least-significant byte configures the positive jog input (positioning in positive
direction) and the most significant byte influences the negative jog input. The alloca-
tion is bit-wise, i.e. bit 0 of the parameter is linked to input 0.
With parameter POPRT the input port is defined (Í 543-POPRT - Port configuration
for input assignment, page 128).
Values:
Minimum Maximum Factory set. Unit MODE SMARTCARD Type
0000H FFFFH 2040H R1W4 POMOD USIGN16
Note:
The parameter is only required for parameter setting via interface. In D
RIVEMANAGER
operation the value is calculated by way of the settings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lust MASTERCONTROL MC6000 Series and is the answer not in the manual?

Lust MASTERCONTROL MC6000 Series Specifications

General IconGeneral
BrandLust
ModelMASTERCONTROL MC6000 Series
CategoryController
LanguageEnglish