Date Code 20130214 Instruction Manual SEL-2414 Transformer Monitor
Section 6
Instruction Manual
Settings
Overview
The SEL-2414 Transformer Monitor stores settings you enter in nonvolatile
memory. Settings are divided into seven setting classes (Device, Logic, Global,
Port, Front-Panel, Report, and DNP settings). In this section, we discuss the fol-
lowing setting classes (see Section 4: Logic Functions settings for Logic settings,
and Appendix D: DNP3 Communications for DNP settings):
1. Device
2. Global
3. Port p (where p = F, 1 (Ethernet), 2, 3, or 4)
4. Front-Panel Set
5. Report
Some setting classes have multiple instances. In the above list, there are four port
setting instances, one for each port. Table 6.1 shows the three different ways in
which you can view or set the device settings.
Setting entry error messages, together with corrective actions, are also presented
in this section to assist correct settings entry. The SEL-2414 settings sheets at the
end of this section list all SEL-2414 settings.
Table 6.1 Methods of Accessing Settings
Serial Port
Commands
a
a
Refer to Section 7: Communications for detailed information on setup and use of the serial
communications port.
Front-Panel HMI
Set/Show Menu
b
b
Refer to Section 8: Front-Panel Operations for detailed information on the front-panel layout,
menus and screens, and operator control pushbuttons.
ACSELERATOR QuickSet
®
SEL
-5030 (PC software)
c
c
Refer to Section 3: Getting Started for detailed information.
Display
Settings
All settings
(SHO command)
All settings All settings
Change
Settings
All settings
(SET command)
All settings All settings