Date _______________
Date Code 20130214 Instruction Manual SEL-2414 Transformer Monitor
SEL-2414 Settings Sheets
Section SET
Instruction Manual
These settings sheets include the definition and input range for each setting in the device. You can access the set-
tings from the device front panel and the serial ports.
Some settings require an optional module (see Section 4: Logic Functions for details).
Some of the settings ranges may be more restrictive than shown, because of settings interdependency
checks performed when new settings are saved. The settings are not case sensitive.
Device Settings (SET Command)
Device Settings
Device Identification (16 characters) DID :=
Terminal ID (16 characters) TID
:=
Transformer Settings
Current Transformer Ratio (1–5000) (Shown if SELECT 4
ACI)
CTR :=
Neutral Current Transformer Ratio (1–5000) (Shown if
SEL
ECT 4 ACI)
CTRN
:=
X Currents Transformer Ratio (1–5000)
(Shown if SEL
ECT 3 ACI/3 AVI and ETHERM W)
CTRX
:=
X Current, Winding 1 Transformer Ratio (1–5000)
(Shown if SEL
ECT 3ACI/3 AVI, and ETHERM = W)
CTRX_W1
:=
X Current, Winding 2 Transformer Ratio (1–5000)
(Shown if SEL
ECT 3ACI/3 AVI, and ETHERM = W)
CTRX_W2
:=
X Current, Winding 3 Transformer Ratio (1–5000)
(Shown if SEL
ECT 3ACI/3 AVI, and ETHERM = W)
CTRX_W3
:=
Potential Transformer Ratio (1.00–10000.00) (SEL
ECT
3ACI/3 AVI or 3 AVI)
PTR :=
For the following settings, x is the card position (3, 4, 5, or 6);
y indicates input number 1–8 for an 8 AI card or 1–4 for a 4 AI/4 AO card.
Demand Metering
Enable Demand Metering EDEM :=
Demand Meter Time Constant (5, 10, 15, 30, 60 min) DMTC
:=
Analog Input x01 Settings
AIx01 Instrument Tag Name (8 characters 0–9, A–Z, _) AIx01NAM :=
AIx01 Type (I, V) AIx01TYP
:=
If AIx01TYP = I
AIx01 Low (–20.480 to +20.480; mA) AIx01L
:=
AIx01 High (–20.480 to +20.480; mA) AIx01H
:=
If AIx01TYP = V
AIx01 Low (–10.240 to +10.240 V) AIx01L
:=
AIx01 High (–10.240 to +10.240 V) AIx01H
:=
NOTE: Set Warn and Alarm to a value between Engr Low and Engr High settings.