Date Code 20130214 Instruction Manual SEL-2414 Transformer Monitor
Firmware Upgrade Instructions
IEC 61850 CID File Upgrade Instructions
IEC 61850 CID File Upgrade Instructions
Verify or Restart
IEC 61850 Operation
(Optional)
SEL-2414 series devices with optional IEC 61850 protocol require the presence
of one valid CID file to enable the protocol. You should only transfer a CID file
to the device if you want to implement a change in the IEC 61850 configuration
or if new SEL-2414 firmware does not support the current CID file version. If
you transfer an invalid CID file, the device will disable the IEC 61850 protocol,
as it no longer has a valid configuration. To restart IEC 61850 protocol operation,
you must transfer a valid CID file to the device.
Perform the following steps to verify that the IEC 61850 protocol is still opera-
tional after an SEL-2414 firmware upgrade and if not, re-enable it. This proce-
dure assumes that IEC 61850 was operational with a valid CID file immediately
before initiating an SEL-2414 firmware upgrade.
Step 1. Establish an FTP connection to the SEL-2414 Ethernet port.
Step 2. Open the ERR.TXT file for reading.
If the ERR.TXT file contains error messages relating to CID file
parsing, this indicates that the device has disabled the IEC 61850
protocol. If this file is empty, the device found no errors during
CID file processing and IEC 61850 should remain enabled. Skip to
Step 3 if ERR.TXT is empty.
If the IEC 61850 protocol has been disabled because of an
upgrade-induced CID file incompatibility, you can use
ACSELERATOR Architect
®
SEL-5032 Software to convert the
existing CID file and make it compatible again.
a. Install the
ACSELERATOR Architect software upgrade that
supports your required CID file version.
b. Run
ACSELERATOR Architect and open the project that
contains the existing CID file for the device.
c. Download the CID file to the device.
Upon connecting to the device,
ACSELERATOR Architect
will detect the upgraded SEL-2414 firmware and prompt
you to allow it to convert the existing CID file to a
supported version. Once converted, downloaded, and
processed, the valid CID file allows the device to re-enable
the IEC 61850 protocol in its original configuration.
Step 3. In the Telnet session, type GOO <Enter> or you can also execute
GOO from a 2AC prompt on a serial port connection.
Step 4. View the GOOSE status and verify that the transmitted and
received messages are as expected.