F.13IEC 61850 Communications
ACSI Conformance Statements
Date Code 20130214 Instruction Manual SEL-2414 Transformer Monitor
GOOSE Services
Conformance
Statement
ACSI Conformance Statements
Tab le F.1 8 G O OS E Co n for m an c e
Subscriber Publisher Value/Comment
GOOSE Services Y Y
SendGOOSEMessage Y
GetGoReference
GetGOOSEElementNumber
GetGoCBValues Y
SetGoCBValues
GSENotSupported
GOOSE Control Block (GoCB) Y
Table F.19 ACSI Basic Conformance Statement
Client/Subscriber Server/Publisher SEL-2414 Support
Client-Server Roles
B11 Server side (of Two-Party Applica- - cl
a
YES
B12 Client side (of Two-Party Applica- cl
a
-
SCMS Supported
B21 SCSM: IEC 61850-8-1 used YES
B22 SCSM: IEC 61850-9-1 used
B23 SCSM: IEC 61850-9-2 used
B24 SCSM: other
Generic Substation Event Model (GSE)
B31 Publisher side - O
b
YES
B32 Subscriber side O
b
-YES
Transmission of Sampled Value Model (SVC)
B41 Published side - O
b
B42 Subscriber side O
b
-
a
c1 shall be mandatory if support for LOGICAL-DEVICE model has been declared.
b
O = Optional.
Table F.20 ACSI Models Conformance Statement (Sheet 1 of 2)
Client/Subscriber Server/Publisher SEL-2414 Support
If Server Side (B11) Supported
M1 Logical device c2
a
c2
a
YES
M2 Logical node c3
b
c3
b
YES
M3 Data c4
c
c4
c
YES
M4 Data set c5
d
c5
d
YES
M5 Substation O
e
O
e
M6 Setting group control O
e
O
e
Reporting
M7 Buffered report control O
e
O
e
YES
M7-1 sequence-number YES
M7-2 report-time-stamp YES
M7-3 reason-for-inclusion YES