A.2
SEL-2414 Transformer Monitor Instruction Manual Date Code 20130214
Firmware and Manual Versions
Firmware
SEL-2414-R303-V0-Z007007-D20100624 ➤ Fixed a firmware upgrade issue where the IED, under certain settings
conditions, fails to upgrade settings.
➤ Added capability to use remote analogs, analog inputs, and math vari-
ables as inputs into the thermal model.
➤ Added support for ACSELERATOR QuickSet Design Templates stor-
age.
➤ Added support for additional front-panel LEDs.
➤ Updated the DNP library and added additional Object Variations.
➤ Fixed an issue with DNP over Port 2 fiber.
➤ Changed device functionality to restart when an exception occurs.
20100624
SEL-2414-R302-V0-Z006006-D20100115
➤ Manual update only (see Table A.3). 20100512
SEL-2414-R302-V0-Z006006-D20100115
➤ Added support for Universal Temperature Input card (this includes J,
K, T, & E thermocouples).
➤ Added DNP Frozen Counters.
➤ Added protocol enables for FTP, Telnet, and Modbus.
➤ Corrected an IEC 61850 communications defect where the firmware
incorrectly reads an opcode from flash memory and results in a vector.
➤ Revised firmware for processor update. Previous versions cannot be
upgraded to R302.
20100115
Table A.1 300 Series Firmware Revision History (Sheet 2 of 2)
Firmware Identification (FID) Number Summary of Revisions
Manual
Date Code
Table A.2 200 Series Firmware Revision History
Firmware Identification (FID) Number Summary of Revisions
Manual
Date Code
SEL-2414-R208-V0-Z005005-D20120418 ➤ Corrected an issue with the thermal monitor where a noninteger value
for the voltage setting in TMWNOM caused incorrect calculated top
oil temperature, hot-spot temperature, and loss-of-life calculation.
➤ Corrected an analog quantities defect where an incorrect value for
3I2PD or 3I2P could be referenced if used in an analog compare in a
SEL
OGIC control equation.
➤ Corrected an issue with the thermal monitor alarm logic where the
CSE alarms were not being blocked by their associated bits indicating
healthy top-oil temperature measurement RTD (MTOn_OK).
➤ Corrected an issue where CSALARM can be incorrectly cleared.
➤ Fixed disconnection error with Telnet port and Fast Messages.
➤ Corrected scaling of TnRLOL and TnTLOL quantities in Modbus.
➤ Volatile thermal model data are reset only if any of the thermal settings
are changed.
20120418
SEL-2414-R207-V0-Z005005-D20090624
➤ Corrected settings upgrade issue from SEL-2414 versions prior to
R206.
20090624
SEL-2414-R206-V0-Z005005-D20090311
➤ Added thermal monitor and through-fault monitor capabilities.
➤ Improved IEC 61850 security (see www.selinc.com/privacy.htm for
details).
➤ Added support for optional dual copper Ethernet and single/dual fiber
Ethernet communications.
➤ Added support for SELECT 3 AVI and SELECT 4CT cards.
20090311
SEL-2414-R205-V0-Z004004-D20081111
➤ Updated library version number in IEC 61850 library for new control
capabilities.
20081111
SEL-2414-R204-V0-Z004004-D20081030
➤ Updated IEC 61850 firmware to streamline MMS processing and
improve TCP/IP connections.
➤ Improved security (see www.selinc.com/privacy.htm for details).
20081030
SEL-2414-R203-V0-Z003003-D20080715
➤ Added support for SELECT 4 DI/3 DO card. 20080715
SEL-2414-R202-V0-Z003003-D20080429
➤ Initial version. 20080429