SEL-2414 Transformer Monitor Instruction Manual Date Code 20130214
SEL Communications Processors
SEL Communications Processor Example
Now every time the ISSUE1 condition in the Automatic Messages on Port 3 is
true, the SEL communications processor will send an Unsolicited Write message
to the SEL-2414 and populate Remote Analogs 1–12 with the corresponding
stored data in the SEL communications processor User region on Port 6.
Execute a MET RA or CME RA in the SEL-2414 to retrieve the Remote Analog
data.
=>>SET R TERSE <Enter>
Report
SER Chatter Criteria
Auto-Removal EN (N,Y) ESERDEL := N ? <Enter>
SER Trigger Lists
SERn = Up to 24 Device-Word elements separated by spaces or commas.
Use NA to disable setting.
SER Trigger List SER1 (24 Device Word bits)
SER1 := NA
? <Enter>
SER Trigger List SER2 (24 Device Word bits)
SER2 := NA
? <Enter>
SER Trigger List SER3 (24 Device Word bits)
SER3 := NA
? <Enter>
SER Trigger List SER4 (24 Device Word bits)
SER4 := NA
? <Enter>
Event Report Set
Event Trigger (SELogic)
ER := NA
? <Enter>
Event Length (15,64 cyc) LER := 15 ? <Enter>
Prefault Length (OFF,1-10 cyc) PRE := 4 ? <Enter>
Fast Message Remote Analog Settings
Remote Analog Value Type (I,F,L) RA01TYPE:= I ? I <Enter>
Remote Analog Value Type (I,F,L) RA02TYPE:= I ? I <Enter>
Remote Analog Value Type (I,F,L) RA03TYPE:= I ? I <Enter>
Remote Analog Value Type (I,F,L) RA04TYPE:= I ? I <Enter>
Remote Analog Value Type (I,F,L) RA05TYPE:= I ? F <Enter>
Remote Analog Value Type (I,F,L) RA06TYPE:= I ? F <Enter>
Remote Analog Value Type (I,F,L) RA07TYPE:= I ? F <Enter>
Remote Analog Value Type (I,F,L) RA08TYPE:= I ? F <Enter>
Remote Analog Value Type (I,F,L) RA09TYPE:= I ? L <Enter>
Remote Analog Value Type (I,F,L) RA10TYPE:= I ? L <Enter>
Remote Analog Value Type (I,F,L) RA11TYPE:= I ? L <Enter>
Remote Analog Value Type (I,F,L) RA12TYPE:= I ? L <Enter>
Remote Analog Value Type (I,F,L) RA13TYPE:= I ? END <Enter>
Save changes (Y,N)? Y <Enter>
Settings Saved
=>>
Figure C.6 Setting Remote Analogs RA01 Through RA13