10.2.2 Example of a Diagnostics Message Indicated by a Flashing
Sequence
The example below illustrates the representation of a diagnostics message via a
flashing sequence. The I/O LED indicates a data error on the local bus. The data
error is caused by the removal of an I/O module located at the 6th position of the
bus node.
Initiation of the Start Phase
1. The I/O LED flashes for 1 cycle at about 10 Hz (10 flashes/second).
2. This is followed by a pause of about one second.
Error Code 4: Data Error in the Local Bus
3. The I/O LED flashes for 4 cycles of about 1Hz.
4. This is followed by a pause of about 1 second.
Error Argument 5: I/O Module at the 6th Slot
5. The I/O LED flashes for 5 cycles at 1 Hz.
This indicates that a disruption has occurred at the local bus downcircuit of
the 5th I/O module.
6. The blink code starts flickering when the start phase is initiated again. If
there is only one error, this process is repeated.

Table of Contents

Other manuals for WAGO PFC100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO PFC100 and is the answer not in the manual?

WAGO PFC100 Specifications

General IconGeneral
BrandWAGO
ModelPFC100
CategoryController
LanguageEnglish

Related product manuals