308 Appendix WAGO-I/O-SYSTEM 750
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
The Binary Space Modules behave alternatively like 2 channel digital input
modules or output modules and seize depending upon the selected settings 1, 2,
3 or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are occupied then either
in the process input or the process output image.
Table 263: Binary Space Module 750-622 (with Behavior like 2 Channel Digital Input)
Input and Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
(Data bit
DI 8)
(Data bit
DI 7)
(Data bit
DI 6)
(Data bit
DI 5)
(Data bit
DI 4)
(Data bit
DI 3)
Data bit
DI 2
Data bit
DI 1