EasyManua.ls Logo

WAGO PFC100 - Perform Firmware Downgrade

WAGO PFC100
318 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO-I/O-SYSTEM 750 Service 253
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
11.2.2 Perform Firmware Downgrade
Do not switch the controller off!
The controller can be damaged by interrupting the downgrade process.
Do not switch the controller off during the downgrade process and do not
disconnect the power supply!
Note the firmware version
For devices with a factory installation of a firmware >= FW 05, a simple
downgrade to a version <= FW 04 is not possible!
Use a special downgrade image.
Proceed as follows if you want to downgrade the controller to an earlier firmware
version:
1. Save your application and the controller settings.
2. Switch off the controller.
3. Insert the memory card with the new firmware image into the memory card
slot. Use a special downgrade image if necessary.
4. Switch on the controller.
5. After booting the controller, launch the WBM “Create Boot Image” page
(you may have to temporarily change the IP address).
6. Create a new boot image on the internal memory.
7. Switch off the controller after completing the process.
8. Remove the memory card.
9. Switch on the controller.
The controller can now be started with the new firmware version.

Table of Contents

Other manuals for WAGO PFC100

Related product manuals