WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 269
750-8100 PFC100; 2ETH; ECO
Manual
Version 1.6.0, valid from FW Version 03.02.02(14)
14.2.2 Special Notes Regarding ANSI/ISA Ex
For ANSI/ISA Ex acc. to UL File E198726, the following additional requirements
apply:
Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only
ETHERNET connections are used exclusively for connecting to computer
networks (LANs) and may not be connected to telephone networks or
telecommunication cables
WARNING The radio receiver module 750-642 may only be used to
connect to external antenna 758-910!
WARNING Product components with fuses must not be fitted into circuits
subject to overloads!
These include, e.g., motor circuits.
WARNING When installing I/O module 750-538, “Control Drawing No.
750538” in the manual must be strictly observed!
Additional Information
Proof of certification is available on request.
Also take note of the information given on the operating and assembly
instructions.
The manual, containing these special conditions for safe use, must be readily
available to the user.

Table of Contents

Other manuals for WAGO PFC100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO PFC100 and is the answer not in the manual?

WAGO PFC100 Specifications

General IconGeneral
BrandWAGO
ModelPFC100
CategoryController
LanguageEnglish

Related product manuals